UP

Reduced energy consumption sewage pumps with IE3 motors. Its anti blockage design with vortex impeller leads to big free passage.

Technical Data
  • ø Discharge bore mm: 80 - 100
  • Type of Fluid: Sewage
  • Max. Solid Handling mm: 60 - 100
  • Max. PH Value: 6-14
  • Max. Capacity l/min: 1100 - 3320
  • Max. Head m: 8.80 - 19.1
  • Motor output kW: 3,0 - 7,5
  • Phase / Voltage: 3-phase / 400V / 50Hz
Performance curve
1 O
2 O
Specifications
Model Colour code curve ø Discharge bore mm Type of Fluid Max. Solid Handling mm Max. PH Value Max. Capacity l/min Max. Head m Motor output kW Phase / Voltage Monitoring
free standing with guide rail fitting
80UP43.0 -C165 TOS80UP43.0 -C165 1 80 Sewage 65 6-14 2040 8.80 3,0 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
80UP44.0 -D210 TOS80UP44.0 -D210 2 80 Sewage 60 6-14 1100 15.7 4,0 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
80UP45.5 -D220 TOS80UP45.5 -D220 3 80 Sewage 60 6-14 2430 16.6 5,5 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
80UP47.5 -D235 TOS80UP47.5 -D235 4 80 Sewage 60 6-14 2660 19.1 7,5 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
100UP44.0 -B190 TOS100UP44.0 -B190 5 100 Sewage 100 6-14 2320 11.4 4,0 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
100UP45.5 -B210 TOS100UP45.5 -B210 6 100 Sewage 100 6-14 2740 14.3 5,5 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
100UP47.5 -B220 TOS100UP47.5 -B220 7 100 Sewage 100 6-14 3320 16 7,5 3-phase / 400V / 50Hz double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 80
Type of Fluid Sewage
Max. Solid Handling mm 65
Max. PH Value 6-14
Max. Capacity l/min 2040
Max. Head m 8.80
Motor output kW 3,0
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 80
Type of Fluid Sewage
Max. Solid Handling mm 60
Max. PH Value 6-14
Max. Capacity l/min 1100
Max. Head m 15.7
Motor output kW 4,0
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 80
Type of Fluid Sewage
Max. Solid Handling mm 60
Max. PH Value 6-14
Max. Capacity l/min 2430
Max. Head m 16.6
Motor output kW 5,5
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 80
Type of Fluid Sewage
Max. Solid Handling mm 60
Max. PH Value 6-14
Max. Capacity l/min 2660
Max. Head m 19.1
Motor output kW 7,5
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 100
Type of Fluid Sewage
Max. Solid Handling mm 100
Max. PH Value 6-14
Max. Capacity l/min 2320
Max. Head m 11.4
Motor output kW 4,0
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 100
Type of Fluid Sewage
Max. Solid Handling mm 100
Max. PH Value 6-14
Max. Capacity l/min 2740
Max. Head m 14.3
Motor output kW 5,5
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
ø Discharge bore mm 100
Type of Fluid Sewage
Max. Solid Handling mm 100
Max. PH Value 6-14
Max. Capacity l/min 3320
Max. Head m 16
Motor output kW 7,5
Phase / Voltage 3-phase / 400V / 50Hz
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
General
ø Discharge bore mm 80 - 100
Discharge Connection DN 100 EN 1092-2, DN 80 EN 1092-2
Pumping Fluid
Type of Fluid Sewage
Temperature 0-40°C
Max. Solid Handling mm 60 - 100
Max. PH Value 6-14
Max. Capacity l/min 1100 - 3320
Max. Head m 8.80 - 19.1
Pump
Components
Impeller Vortex impeller
Mechanical Seal Dual mechancial seal in oil bath
Material
Impeller Grey iron casting EN-GJL-250
Casing Grey iron casting EN-GJL-250
Suction Plate Grey iron casting EN-GJL-250
Pump Body Grey iron casting EN-GJL-250
Mechanical Seal Silicon Carbide
Motor
Motor output kW 3,0 - 7,5
Starting method direct online , star/delta
Type, Poles Induction motor, 4 poles, IP68
Insulation Insulation class H
Phase / Voltage 3-phase / 400V / 50Hz
r.p.m. 1450 - 1460
Motor Protector (built-in) bimetal thermal protectors (Klixon) in series
Monitoring double leakage sensor (mechanical seals chamber and stator housing) 1 signal
Rated Current 6.60 - 14.50
Material
Shaft AISI 431
Cable S1RN8F 4G2.5 + 3x1, S1RN8F 7G1.5 + 3x1
Cable Length 10m
Others
Dry Weight Kg 148 - 218
Dimensions - in mm
W1: lowest running water level
  • 80UP44.0 -D210
W1: lowest running water level
  • 80UP43.0 -C165
W1: lowest running water level
  • 80UP45.5 -D220
W1: lowest running water level
  • 80UP47.5 -D235
W1: lowest running water level
  • 100UP44.0 -B190
W1: lowest running water level
  • 100UP45.5 -B210
W1: lowest running water level
  • 100UP47.5 -B220
ModelA
80UP43.0 -C165-
80UP44.0 -D210-
80UP45.5 -D220-
80UP47.5 -D235-
100UP44.0 -B190-
100UP45.5 -B210-
100UP47.5 -B220-
Dimensions - in mm
  • 80UP43.0 -C165
W1: lowest running water level
  • 80UP44.0 -D210
W1: lowest running water level
  • 80UP45.5 -D220
W1: lowest running water level
  • 80UP47.5 -D235
W1: lowest running water level
  • 100UP44.0 -B190
W1: lowest running water level
  • 100UP45.5 -B210
W1: lowest running water level
  • 100UP47.5 -B220
W1: lowest running water level
ModelA
80UP43.0 -C165-
80UP44.0 -D210-
80UP45.5 -D220-
80UP47.5 -D235-
100UP44.0 -B190-
100UP45.5 -B210-
100UP47.5 -B220-

UP series combines the proven advantages of vortex hydraulics with enhanced energy efficiency, thanks to the integration of high-performance IE3 motors.

Its vortex impeller and full free passage construction allow for safe and reliable handling of wastewater containing solids and fibrous materials which this pump be suitable for: Biological liquids and wastewater, Civil and industrial lifting, Wastewater treatment plants and livestock farms, etc...